Room CFM Calculator
Calculate room CFM from dimensions and air changes per hour, convert AC BTU/h to airflow, and size an evaporative cooler.
Calculate
Enter either air changes per hour or required airflow to calculate the other from room volume.
- Required airflow (CFM)
- 336
- Room volume (cu ft)
- 3,360
- Air changes per hour
- 6
Calculation formulas
- Room volume = length × width × ceiling height.
- CFM = room volume × ACH / 60; ACH = CFM × 60 / room volume.
| Scenario | Room volume (cu ft) | Required airflow (CFM) | Air changes per hour |
|---|---|---|---|
| 3 ACH | 3,360 | 168 | 3 |
| 6 ACH | 3,360 | 336 | 6 |
| 12 ACH | 3,360 | 672 | 12 |
400 CFM per ton is a nominal coil airflow reference. Air changes here describe equivalent recirculation through the AC; sensible cooling describes dry-bulb heat removal at standard air density.
- Required airflow (CFM)
- 333.33
- Room volume (cu ft)
- 3,360
- Air changes per hour
- 5.95
- Sensible cooling (BTU/h)
- 7,200
Calculation formulas
- CFM = cooling capacity / 12,000 × CFM per ton.
- ACH = CFM × 60 / room volume.
- Sensible cooling = 1.08 × CFM × temperature difference.
| Scenario | Required airflow (CFM) | Air changes per hour | Sensible cooling (BTU/h) |
|---|---|---|---|
| 350 CFM per ton | 291.67 | 5.21 | 6,300 |
| 400 CFM per ton | 333.33 | 5.95 | 7,200 |
| 450 CFM per ton | 375 | 6.7 | 8,100 |
The climate presets span 20, 30 and 40 ACH for airflow planning. Direct evaporative cooling works best in dry air with outdoor air supply and an open exhaust path. High humidity limits cooling and increases indoor moisture.
- Required airflow (CFM)
- 2,240
- Room volume (cu ft)
- 3,360
- Air changes per hour
- 40
Calculation formulas
- CFM = room volume × climate ACH / 60.
- Humid = 20 ACH; moderate = 30 ACH; hot and dry = 40 ACH.
| Scenario | Room volume (cu ft) | Required airflow (CFM) | Air changes per hour |
|---|---|---|---|
| Humid | 3,360 | 1,120 | 20 |
| Moderate | 3,360 | 1,680 | 30 |
| Hot and dry | 3,360 | 2,240 | 40 |
How to use
Enter room length, width, and ceiling height in feet (default 20 × 21 × 8 ft, or 3,360 cu ft), then choose Air changes, AC airflow, or Evaporative cooler to calculate required airflow in cubic feet per minute (CFM). Room dimensions stay synced when switching tabs, with supported ranges of 1 to 300 ft for length and width and 1 to 30 ft for ceiling height.
Air changes
Use Air changes for room ventilation, exhaust planning, and outdoor air-exchange targets, converting between air changes per hour (ACH, default 6 ACH; presets at 3, 6, and 12 ACH) and Required airflow (CFM) (default 336 CFM). Editing Air changes per hour calculates CFM from room volume, while typing a target value into Required airflow (CFM) solves backward for the resulting ACH.
AC airflow
Use AC airflow to size recirculated cooling-coil airflow across the 350 to 450 CFM per ton range (400 CFM per ton default; presets at 350, 400, and 450) and check dry-bulb sensible cooling across a 0°F to 60°F Temperature difference (°F) (default 20°F). This mode applies to air recirculated across an evaporator coil from a unit's Cooling capacity (BTU/h) (default 10,000 BTU/h) rather than outdoor fresh-air exchange.
Evaporative cooler
Use Evaporative cooler for dry-climate, once-through evaporative cooling with an outdoor air intake and an open exhaust window, selecting Humid (20 ACH), Moderate (30 ACH), or Hot and dry (40 ACH default). Direct evaporative cooling relies on dry ambient air to evaporate water; the temperature drop depends on the gap between outdoor dry-bulb and wet-bulb temperatures and on the media efficiency, so humid air gives a smaller drop and adds indoor moisture. At 95°F and 50% relative humidity, a direct evaporative cooler still delivers a drop of about 11°F.
Formula
Room airflow equals room volume multiplied by air changes per hour divided by 60 (CFM = Length × Width × Ceiling height × ACH / 60), while AC coil airflow scales refrigeration tons (BTU/h / 12,000) by 350 to 450 CFM per ton and sensible heat removal equals 1.08 × CFM × Temperature difference (°F).
Room volume (cu ft) = Length (ft) × Width (ft) × Ceiling height (ft)
Air changes mode:
CFM = Room volume × ACH / 60
ACH = CFM × 60 / Room volume
AC airflow mode:
Refrigeration tons = Cooling capacity (BTU/h) / 12,000
CFM = Refrigeration tons × CFM per ton (350–450 CFM/ton)
Equivalent ACH = CFM × 60 / Room volume
Sensible cooling = 1.08 × CFM × Temperature difference (°F)
Evaporative cooler mode:
CFM = Room volume × Climate ACH / 60
Climate ACH presets = 20 (Humid) | 30 (Moderate) | 40 (Hot and dry)
The 1.08 constant represents standard air density and specific heat (0.075 lb/cu ft × 0.24 BTU/(lb·°F) × 60 min/hr), yielding dry-bulb sensible cooling capacity without latent moisture removal.
Worked example
Using the default 20 × 21 × 8 ft room (3,360 cu ft), 6 ACH ventilation requires 336 CFM, a 10,000 BTU/h air conditioner at 400 CFM per ton moves 333.33 CFM with 7,200 BTU/h of sensible cooling at a 20°F temperature difference, and the Hot and dry evaporative cooler preset at 40 ACH requires 2,240 CFM.
Room volume = 20 × 21 × 8 = 3,360 cu ft
1. Air changes (6 ACH default):
CFM = 3,360 × 6 / 60 = 336 CFM
2. AC airflow (10,000 BTU/h, 400 CFM/ton, 20°F delta):
CFM = (10,000 / 12,000) × 400 = 333.33 CFM
Equivalent ACH = 333.3333 × 60 / 3,360 = 5.95 ACH
Sensible cooling = 1.08 × 333.3333 × 20 = 7,200 BTU/h
3. Evaporative cooler (Hot and dry = 40 ACH):
CFM = 3,360 × 40 / 60 = 2,240 CFM
(Moderate 30 ACH = 1,680 CFM; Humid 20 ACH = 1,120 CFM)
In the AC airflow example, 7,200 BTU/h is the sensible portion of the 10,000 BTU/h total cooling rate, leaving 2,800 BTU/h for latent moisture removal when indoor air requires dehumidification.
Room CFM reference table
For standard 8 ft ceilings at 4 to 8 ACH, room airflow ranges from 64 to 128 CFM in a 10 × 12 ft bedroom (960 cu ft) up to 224 to 448 CFM in a 20 × 21 ft room (3,360 cu ft).
| Room Size (8 ft ceiling) | Room Volume | 4 ACH (CFM) | 6 ACH (CFM) | 8 ACH (CFM) |
|---|---|---|---|---|
| 12 × 12 × 8 ft | 1,152 cu ft | 77 | 115 | 154 |
| 10 × 12 × 8 ft bedroom | 960 cu ft | 64 | 96 | 128 |
| 300 sq ft × 8 ft | 2,400 cu ft | 160 | 240 | 320 |
| 20 × 21 × 8 ft | 3,360 cu ft | 224 | 336 | 448 |
Values in the table follow CFM = Length × Width × Height × ACH / 60 rounded to the nearest whole CFM.
Common mistakes
Mixing up recirculated AC coil airflow with outdoor air changes, ignoring ceiling height above 8 ft, or sizing total BTU/h from the 1.08 sensible heat equation leads to miscalculated fan and equipment requirements.
- Treating recirculated AC airflow as fresh-air ventilation: A room air conditioner circulating 333.33 CFM at 400 CFM per ton passes existing indoor air repeatedly over a cold coil; it does not deliver 5.95 ACH of outdoor fresh air unless a separate ventilation path exists.
- Confusing sensible cooling with total cooling capacity: The
1.08 × CFM × ΔTformula calculates sensible (temperature-drop) cooling only (7,200 BTU/h in the default example), omitting latent dehumidification load handled by the compressor. - Estimating airflow from floor area without ceiling height: A 300 sq ft room with an 8 ft ceiling holds 2,400 cu ft (240 CFM at 6 ACH), whereas a 12 ft ceiling over the same 300 sq ft footprint holds 3,600 cu ft and requires 360 CFM (50% more airflow) for 6 ACH.
- Operating evaporative coolers without an open exhaust path or in humid weather: Evaporative coolers push 20 to 40 ACH of outdoor air into a space and require open windows or exhaust vents so humidified air leaves the room; as outdoor humidity rises, the dry-bulb to wet-bulb gap narrows and the achievable temperature drop shrinks.
- Running cooling coils outside 350 to 450 CFM per ton: Airflow below 350 CFM per ton drops coil surface temperature and invites frost or icing, while airflow above 450 CFM per ton shortens moisture contact time on the coil and raises air noise.
Related calculators
Pair this airflow estimate with CoolingSpecs room load and tonnage tools to size total cooling capacity in BTU/h and refrigeration tons.
- Air Conditioner BTU & Room Size Calculator: Calculate adjusted room cooling load in BTU/h from floor area, ceiling height, solar exposure, insulation, occupants, and kitchen heat before setting AC airflow.
- AC Tonnage Calculator: Convert adjusted room cooling demand into refrigeration tons (1 ton = 12,000 BTU/h) and match standard capacity tiers.
FAQ
How do you calculate CFM for a room?
Multiply room volume (Length × Width × Ceiling height) by the target air changes per hour (ACH) and divide by 60 (CFM = L × W × H × ACH / 60), which yields 336 CFM for a 20 × 21 × 8 ft room (3,360 cu ft) at 6 ACH. For air conditioner coil airflow, divide cooling capacity in BTU/h by 12,000 and multiply by 350 to 450 CFM per ton (default 400 CFM/ton, giving 333.33 CFM for a 10,000 BTU/h unit); for direct evaporative coolers, multiply room volume by 20, 30, or 40 ACH and divide by 60.
How many CFM for a 12x12 room?
A 12 × 12 ft room with an 8 ft ceiling (1,152 cu ft) needs 115 CFM at 6 ACH (exact: 115.2 CFM), or 77 CFM at 4 ACH and 154 CFM at 8 ACH. If cooled by a 5,000 BTU/h room air conditioner at 400 CFM per ton, recirculated coil airflow is 166.67 CFM, while a Hot and dry evaporative cooler at 40 ACH requires 768 CFM.
How many CFM for a 300 sq ft room?
A 300 sq ft room with an 8 ft ceiling (2,400 cu ft) needs 240 CFM at 6 ACH, 160 CFM at 4 ACH, and 320 CFM at 8 ACH. For AC coil recirculation, a baseline 7,000 BTU/h unit for a 300 sq ft space moves 233.33 CFM at 400 CFM per ton, while a Hot and dry evaporative cooler at 40 ACH moves 1,600 CFM.
How much CFM is needed for a bedroom?
A standard 10 × 12 ft bedroom with an 8 ft ceiling (960 cu ft) needs 64 CFM at 4 ACH, 96 CFM at 6 ACH, or 128 CFM at 8 ACH for room air exchange. Larger 12 × 12 × 8 ft bedrooms need 115 CFM at 6 ACH, and a 5,000 to 6,000 BTU/h bedroom AC unit at 400 CFM per ton circulates 166.67 to 200 CFM across its cooling coil.
Related calculators
Air Conditioner BTU & Room Size Calculator
Room cooling demand from area, envelope and internal heat gains.
Mini-Split Zone & System Capacity Calculator
Connected capacity, simultaneous output and minimum turndown.
Window Air Conditioner & Wall Sleeve Fit Calculator
Opening clearance, chassis geometry and outdoor airflow.
Air Conditioner Electricity, Amps & Cost Calculator
Running watts, power factor, circuit limits and monthly energy.
BTU, Tons & Watts Converter
Convert thermal capacity, electrical input and portable ratings.
SEER2 & CEER Energy Savings Calculator
Compare annual energy and ten-year utility savings.
Heat Pump Sizing & Low-Temperature Capacity Calculator
Heating delivery, demand and thermal balance point.
AC Operating Cost Calculator
Seasonal cooling and delivered heating utility costs.
AC Backup Power Calculator
Generator starting load and battery runtime.
Garage AC BTU Calculator
Garage cooling load, door leakage and workshop equipment.
AC Tonnage Calculator
Calculate room AC tonnage from floor area, ceiling height, sun exposure, insulation and internal gains, with the matching BTU/h capacity tier.
BTU Heating Calculator
Estimate room heating BTU/h and thermal kW from winter design temperatures, envelope U-values and air exchange, then size a ductless heat pump.