AC Backup Power Calculator

Generator starting load and battery runtime.

Engineering workspace

Calculate

Portable generator capacity

Portable generators operate outdoors at least 20 ft from the home, with exhaust directed away from doors, windows and vents. A listed transfer switch or approved interlock installed by a licensed electrician isolates house wiring from utility power. Direct appliance connections use equipment-rated cords; household outlets never receive generator backfeed.

Generator running and surge marginGenerator power marginRequired running1,200 WRated running2,000 WRequired startup3,200 WRated surge3,500 W
Required steady load
1,200 W
Peak startup load
3,200 W
Running headroom
66.67 %
Surge headroom
9.38 %
Generator capacity
Pass
Calculation formulas
  • Steady load = AC running watts + concurrent load; startup load = AC running watts × startup multiplier + concurrent load.
  • Headroom = (generator rating − required load) / required load × 100%. Both running and surge ratings must meet their respective load.
Scenario comparisons
ScenarioRequired steady loadPeak startup loadGenerator capacity
Fixed-speed compressor1,200 W3,200 WPass
Inverter soft-start1,200 W1,400 WPass
Lower surge rating1,200 W3,200 WFail

Generator running and startup ratings

The running requirement combines AC input watts and other outage loads. Fixed-speed compressor startup can require several times running wattage; inverter soft-start generally reduces the startup multiplier. Both generator ratings must accommodate the respective load, with nameplate locked-rotor or startup values taking precedence.

Battery energy and inverter compatibility

Usable battery watt-hours multiplied by the inverter conversion efficiency gives available AC-side energy. Average load combines compressor duty and concurrent loads. Runtime and continuous or surge output are separate requirements: battery capacity determines time, and inverter ratings determine power compatibility.

Outdoor generator and electrical separation

Portable generators run outdoors at least 20 ft from the home, with exhaust directed away from openings. A listed transfer switch or approved interlock installed by a licensed electrician isolates utility service from backup supply.