Heat Pump Sizing & Low-Temperature Capacity Calculator

Heating delivery, demand and thermal balance point.

Engineering workspace

Calculate

Winter capacity and thermal balance

The retention anchors represent generic system classes. Capacity tables at the design temperature govern actual equipment sizing; below −5°F the chart extends the final anchor slope, bounded at zero. EPA 608-certified technicians handle refrigerant circuits.

Heat pump capacity / heating demandHeat pump capacity / heating demandBTU/h0-106,000512,0002018,0003524,00050Outdoor °FHeat pump outputBuilding demand15.3°F balance
Delivered heating capacity
10,800 BTU/h
47°F capacity retained
45 %
Building heating demand
18,000 BTU/h
Surplus / deficit
-7,200 BTU/h
Supplemental heat
7,200 BTU/h
Resistance heat equivalent
2.11 kW
Thermal balance point
15.29 °F

At the design temperature, supplemental heat covers the capacity deficit.

Calculation formulas
  • Building UA = reference load / (65°F − reference temperature). Heating demand = UA × max(0, 65°F − outdoor temperature).
  • Output = 47°F rating × piecewise retention (47°F: 100%; 17°F: 65% / 90%; 5°F: 45% / 80%; −5°F: 30% / 70%).
  • Balance point solves delivered output = building demand; resistance supplement kW = positive deficit / 3,412.14163.
Scenario comparisons
ScenarioDelivered heating capacityBuilding heating demandSurplus / deficit
Standard at 5°F10,800 BTU/h18,000 BTU/h-7,200 BTU/h
Cold-climate at 5°F19,200 BTU/h18,000 BTU/h1,200 BTU/h
Cold-climate at −15°F14,400 BTU/h24,000 BTU/h-9,600 BTU/h

Heating capacity at cold outdoor temperatures

A heat pump rated at 47°F delivers a fraction of its nameplate output as outdoor temperature falls. The generic standard and cold-climate curves interpolate between their four reference anchors; actual capacity tables identify equipment-specific low-ambient limits.

The thermal balance point

Building demand rises as the difference between the 65°F indoor balance setpoint and outdoor temperature grows. The intersection of building load and available heat pump output is the thermal balance point. Below it, the positive demand deficit is the supplemental heat requirement.

Cooling and heating equipment selection

Cooling load remains a separate capacity requirement, calculated from the room envelope and internal heat gains. A licensed electrician establishes supplemental heat circuit capacity, and EPA 608-certified HVAC technicians handle refrigerant connections.