Glossary / Reference directory

Room AC & Ductless HVAC Glossary

This glossary defines the standalone thermodynamic, psychrometric, airflow, electrical, and efficiency-rating terms used in US residential room air conditioner and ductless mini-split engineering, separating heat-removal capacity from energy efficiency and circuit demand. It does not replace room-by-room load calculations, equipment selection, or troubleshooting, which live in dedicated guides and calculators. Every metric here shifts with outdoor and indoor dry-bulb temperatures, airborne moisture levels, air-side pressure drop, and supply voltage or power factor.

What Capacity and Efficiency Ratings Measure (and Confuse)

Capacity ratings measure how fast an air conditioner removes heat in BTU/h or tons, whereas efficiency ratings measure cooling or heating delivered per watt-hour of electrical input and never indicate room size coverage.

Key capacity conversions and portable-AC rating rules:

  • 1 ton = 12,000 BTU/h = 3.51685 kW
  • 1 kW = 3,412.14 BTU/h
  • DOE SACC vs. ASHRAE: DOE Seasonally Adjusted Cooling Capacity (SACC) measures net portable AC cooling after accounting for infiltration and duct heat losses. Single-hose ASHRAE labels run 33%-82% higher than real DOE SACC (SACC is roughly 55%-75% of ASHRAE), so a 14,000 BTU ASHRAE portable typically delivers ~8,000-10,500 BTU SACC for ~300-450 sq ft; always size portables by DOE SACC.
Metric Units What It Measures What It Does Not Measure
Cooling Capacity / DOE SACC BTU/h or tons Net rate of heat removal from the space Electrical draw or seasonal energy efficiency
EER / EER2 BTU/Wh Steady-state cooling efficiency at a fixed test point Room square-footage coverage or peak capacity
CEER BTU/Wh Combined cooling efficiency including standby/off-mode power Real-time cooling capacity in BTU/h
SEER2 BTU/Wh Seasonal cooling efficiency across varying part-load conditions Maximum output at 95°F+ outdoor design peaks
HSPF2 BTU/Wh Seasonal heating efficiency for heat pumps Low-ambient heating capacity retention

For room-level load math and tier boundaries, use the BTU Sizing Calculator and the Room AC Sizing Guide.

Which Psychrometric and Moisture Terms Govern Latent Load?

Dry-bulb temperature alone understates cooling demand in humid climates because an air conditioner must spend part of its capacity condensing water vapor out of the air.

  • Dry-Bulb Temperature: Ordinary air temperature in °F measured without evaporative cooling effects, serving as the baseline for sensible heat loads and equipment rating points.
  • Dew Point: The temperature in °F at which air reaches 100% saturation for its existing moisture content; cooling coils must drop below the room dew point to condense water and dehumidify.
  • Humidity Ratio: The mass of water vapor per unit mass of dry air (often expressed in grains of moisture per lb of dry air), isolating absolute moisture load from temperature-driven relative humidity swings.
  • Cooling Coil Bypass Factor: The fraction of air passing through an evaporator coil that leaves at entering-air conditions rather than reaching the coil's effective surface temperature, reducing both sensible cooling and moisture removal.

Related psychrometric concepts that shift equipment behavior include wet-bulb temperature (which governs evaporative cooling potential; windowless evaporative coolers stop cooling effectively above ~50% outdoor relative humidity), relative humidity (RH, which rises in percentage terms if air is cooled without moisture removal), sensible heat (temperature change without phase change), latent heat (phase-change energy required to condense water vapor), sensible heat ratio (SHR, the fraction of total capacity spent on temperature drop), and moist air enthalpy (total combined sensible and latent heat content).

How Do Airflow and Heat-Transfer Terms Affect Real Output?

Rated BTU/h capacity only reaches the occupied zone when volumetric airflow, air mass density, and heat-exchanger temperature differences stay within design limits.

  • Air Changes per Hour (ACH): The rate at which air volume equal to the room volume is replaced per hour; outdoor air infiltration adds both sensible and latent cooling loads.
  • Air Density: Air mass per unit volume (lb/cu ft), which determines how much heat a given volumetric airflow in CFM can actually carry across a coil.
  • Air-Side Pressure Drop: Static pressure loss across filters, grilles, coils, or portable exhaust ducts; excessive restriction reduces CFM and degrades coil heat transfer.
  • Heat Exchanger Approach Temperature: The temperature difference between leaving air or refrigerant and the interacting heat-transfer medium, indicating how closely a coil approaches thermal equilibrium.

Building-envelope and distribution terms that alter room heat gain include volumetric airflow (CFM), thermal resistance (R-value), solar heat gain coefficient (SHGC, the fraction of solar radiation admitted through glazing), thermal bridging (conductive heat paths through framing or window frames), thermal mass (heat storage that delays peak loads), and thermal stratification (vertical temperature layering in tall rooms). Physical mounting clearances also govern air-side performance; see the Windows and Mounting Guide and Window Fit Calculator.

Which Thermodynamic Cycle Terms Describe Compressor Work?

Refrigeration cycle efficiency falls and compressor power draw rises whenever the pressure and temperature span between the indoor evaporator and outdoor condenser widens.

  • Compressor Compression Ratio: The ratio of absolute discharge pressure to absolute suction pressure; higher ratios increase compressor work per unit of cooling and reduce available capacity during outdoor heat waves.

Related cycle parameters include refrigerant saturation temperature (the pressure-dependent boiling or condensing point), superheat (vapor temperature above saturation entering the compressor), subcooling (liquid temperature below saturation leaving the condenser), temperature lift (the span between cold-side evaporation and hot-side rejection), and temperature glide (the phase-change temperature range of zeotropic refrigerant blends). Under EPA Section 608, charging, recovery, evacuation, flaring, leak-testing, and connecting, opening, or disconnecting pressurized or pre-charged refrigerant lines or condenser service valves require an EPA 608-certified HVAC technician. For multi-head load balancing and capacity-ratio limits, use the Mini-Split Zone Calculator.

How Do Electrical Power, Current, and Circuit Terms Differ?

Real power in watts drives monthly kWh energy use, whereas apparent power in VA, power factor, and waveform distortion govern branch-circuit loading and breaker headroom.

Plain-text electrical and energy formulas:

  • Watts = BTU_h / EER_or_CEER
  • Amps_apparent = Watts / (Voltage * PF) (evaluate PF = 0.92 default and PF = 1.0 resistive lower bound separately from nameplate RLA/FLA)
  • Monthly_kWh = (Watts / 1000) * hours_per_day * duty_factor * days
  • Reference calculation: 12,000 BTU/h at CEER 12.0 on 115V draws 1,000.0 W, 8.70 A at PF = 1.0, and 9.45 A at PF = 0.92; running 8 h/day * 0.70 duty * 30 days consumes 168.0 kWh/month.

Core power-quality and circuit terms:

  • Apparent Power (VA): The product of RMS voltage and RMS current (V * A), which exceeds real watts whenever power factor is below 1.0.
  • Current Crest Factor: The ratio of peak current to RMS current, explaining why inverter-driven compressors can impose higher peak-current demands than resistive loads of equal wattage.
  • Harmonic Distortion: Waveform departure from a pure 60 Hz sinusoid that raises RMS current and conductor heating beyond what real-power watts indicate.

Related electrical concepts include reactive power (VAR, oscillating magnetic/electric field energy), root mean square (RMS, effective AC magnitude), and voltage drop (voltage loss across supply conductors under load). Under NEC 80% continuous branch limits, a 15A circuit (12A continuous) provides 1,440 VA @ 120V / 1,380 VA @ 115V (~1,270 W real @ PF 0.92) or 2,880 VA @ 240V / 2,760 VA @ 230V (~2,540 W real @ PF 0.92); a 20A circuit (16A continuous) provides 1,920 VA @ 120V / 1,840 VA @ 115V (~1,693 W real @ PF 0.92) or 3,840 VA @ 240V / 3,680 VA @ 230V (~3,386 W real @ PF 0.92); and a 30A circuit (24A continuous @ 230V) provides 5,520 VA (~5,078 W real @ PF 0.92). On 208V multi-family service, continuous VA headroom is 13.3% lower than 240V (e.g., 15A -> 2,496 VA / ~2,296 W real @ PF 0.92).

Under NEC 440.62(C), any cord-and-plug room AC sharing a branch circuit with lighting, appliances, or general receptacles is capped at 50% of branch rating (7.5A nameplate on a 15A branch, 10A on a 20A branch), with combined loads kept within the 80% total ceiling. Never infer breaker rating from wall receptacle shape (NEMA 5-15R outlets are permitted on 20A branches under NEC 210.21(B)(3)); verify breaker ampacity only from the panel directory, breaker handle, or a licensed electrician, and read nameplate MCA/MOP values solely for handoff to a licensed electrician. Check circuit headroom with the AC Electricity and Amps Calculator and the Electrical and Energy Guide.

Where Do Sizing, Equipment, and Problem Guides Live?

This glossary owns standalone engineering definitions, while interactive sizing math, unit comparisons, room-specific modifiers, and troubleshooting live in dedicated CoolingSpecs hubs:

Related specifications

32 routes

What Are Air Changes per Hour (ACH)?

Air changes per hour describes the rate at which an air volume equivalent to the room volume is exchanged, with outdoor-air exchange introducing additional sensible and potentially latent cooling loads.

Open reference →

What Is Air Density in HVAC?

Air density determines how much air mass moves through equipment at a given volumetric airflow, affecting the heat-transfer capacity associated with that airflow.

Open reference →

What Is Air-Side Pressure Drop?

Air-side pressure drop is the pressure difference consumed by airflow resistance, which can reduce delivered airflow and constrain heat-transfer capacity at a given fan operating condition.

Open reference →

What Is Apparent Power (VA)?

Apparent power expresses the combined RMS voltage and current demand of an electrical load, helping explain why supply capacity can differ from an AC's real-power consumption in watts.

Open reference →

What Is Cooling Coil Bypass Factor?

Coil bypass factor describes the extent to which leaving air retains entering-air conditions instead of approaching the coil's effective surface condition, affecting sensible and latent cooling performance.

Open reference →

What Is Compressor Compression Ratio?

Compression ratio is the ratio of absolute discharge pressure to absolute suction pressure, with higher ratios generally increasing compressor demands and potentially reducing available capacity.

Open reference →

What Is Current Crest Factor?

Current crest factor is the ratio of repetitive peak current to RMS current, explaining why steady-state electronic loads with similar RMS demand can impose different peak-current requirements on a power source.

Open reference →

What Is Dew Point in Air Conditioning?

Dew point is the temperature at which air becomes saturated at its existing moisture content, establishing when a cooling surface can begin removing water through condensation.

Open reference →

What Is Dry-Bulb Temperature?

Dry-bulb temperature measures ordinary air temperature without evaporative cooling effects and provides a reference for sensible loads and equipment operating conditions.

Open reference →

What Is Harmonic Distortion in HVAC Electrical Loads?

Harmonic distortion occurs when electrical waveforms depart from a pure sinusoid, potentially increasing RMS current, electrical heating, or supply compatibility demands beyond what real-power consumption alone indicates.

Open reference →

What Is Heat Exchanger Approach Temperature?

Approach temperature describes a specified temperature difference between interacting heat-transfer media, indicating how closely a heat exchanger can bring them toward thermal equilibrium.

Open reference →

What Is Humidity Ratio?

Humidity ratio measures the mass of water vapor per unit mass of dry air, allowing moisture loads to be distinguished from temperature-dependent relative humidity.

Open reference →

What Is Latent Heat in Air Conditioning?

Latent heat is energy transferred during a phase change, and an AC must allocate cooling capacity to condensing airborne moisture as well as lowering room temperature.

Open reference →

What Is Moist Air Enthalpy?

Moist air enthalpy represents the combined temperature-related and moisture-related energy content of air, explaining why cooling and drying humid air requires more capacity than temperature reduction alone.

Open reference →

What Is Reactive Power (VAR)?

Reactive power represents oscillating energy exchange associated with electric and magnetic fields under sinusoidal AC conditions, contributing to supply-current demand without equivalent net real-energy consumption.

Open reference →

What Is Refrigerant Saturation Temperature?

Refrigerant saturation temperature is the phase-equilibrium temperature associated with a given pressure, governing the temperature conditions under which a refrigeration cycle absorbs and rejects heat.

Open reference →

What Is Relative Humidity (RH)?

Relative humidity describes water-vapor pressure relative to saturation at the current temperature, making it possible for air to become more humid in percentage terms even as an AC lowers its temperature without removing moisture.

Open reference →

What Is Sensible Heat Ratio (SHR)?

Sensible heat ratio expresses the fraction of total cooling capacity devoted to temperature reduction rather than moisture removal.

Open reference →

What Is Sensible Heat in Air Conditioning?

Sensible heat changes air temperature without changing its phase, so sensible cooling capacity determines how much of a room's temperature-related load an AC can remove.

Open reference →

What Is Solar Heat Gain Coefficient (SHGC)?

Solar heat gain coefficient measures the fraction of incident solar energy entering through glazing as heat, affecting the cooling demand of sun-exposed rooms.

Open reference →

What Is Specific Heat Capacity?

Specific heat capacity describes the energy required to change a unit mass of material by one degree, helping explain the sensible cooling demand of moving air and indoor materials.

Open reference →

What Is Refrigerant Subcooling?

Subcooling is the temperature difference between a refrigerant's saturation reference and its lower liquid temperature at the same pressure, affecting the refrigerant's available cooling effect after expansion.

Open reference →

What Is Refrigerant Superheat?

Superheat is the temperature difference between refrigerant vapor and its saturation reference at the same pressure, reflecting vapor-side operating conditions that influence compressor performance and useful cooling capacity.

Open reference →

What Is Refrigerant Temperature Glide?

Temperature glide is the range of phase-change temperatures exhibited by certain refrigerant mixtures at a given pressure, influencing temperature matching and heat transfer across a coil.

Open reference →

What Is Temperature Lift in an AC or Heat Pump?

Temperature lift is the temperature difference spanned by a refrigeration cycle between its cold and hot sides, with greater lift generally requiring more energy for each unit of heat transferred.

Open reference →

What Is Thermal Bridging?

Thermal bridging occurs when a relatively conductive building element creates a preferential heat-flow path, increasing room cooling loads beyond what the surrounding insulation alone would suggest.

Open reference →

What Is Thermal Mass?

Thermal mass is a material or assembly's ability to store heat, affecting room cooldown time and the timing of peak cooling demand.

Open reference →

What Is Thermal Resistance (R-Value)?

Thermal resistance describes how strongly a material or assembly opposes heat flow, making better-insulated room boundaries less demanding to cool under otherwise equal conditions.

Open reference →

What Is Thermal Stratification?

Thermal stratification is the formation of temperature layers within a space, affecting occupied-zone comfort and how effectively delivered cooling is distributed.

Open reference →

What Is Voltage Drop?

Voltage drop is a reduction in delivered electrical voltage caused by current flowing through supply impedance, potentially affecting compressor operation and the ability of equipment to deliver rated capacity.

Open reference →

What Is Volumetric Airflow (CFM)?

Volumetric airflow measures the volume of air moved per minute, influencing cooling delivery, room air circulation, and air-side heat exchange.

Open reference →

What Is Wet-Bulb Temperature?

Wet-bulb temperature reflects evaporative cooling potential and helps explain both the limitations of evaporative cooling and the moisture burden on refrigerated AC equipment.

Open reference →