Glossary / Technical reference

What Is Reactive Power (VAR)?

Reactive power, measured in volt-amperes reactive (VAR), is the oscillating energy exchanged between a power source and electric or magnetic fields under sinusoidal AC conditions. It contributes directly to total supply current (A) and apparent power (VA) without performing net mechanical cooling work or registering as real energy consumption (W or kWh). In residential air conditioners, reactive power shifts primarily with inductive motor windings (compressors and fans), run capacitors, and the phase angle between supply voltage and current.

Under sinusoidal AC conditions, reactive power (VAR) forms the perpendicular leg of the AC power triangle alongside real power (W) and apparent power (VA). Real power performs the actual thermal work, apparent power sets the total current draw on the branch circuit, and reactive power accounts for the phase-shifted energy sloshing back and forth every half-cycle.

Use these plain-text relationships for single-phase sinusoidal circuits:

  • Apparent Power (VA) = Voltage (V) * Current (A)
  • Real Power (W) = Apparent Power (VA) * Power Factor (PF)
  • Reactive Power (VAR) = sqrt(VA^2 - W^2)
  • Reactive Power (VAR) = Voltage (V) * Current (A) * sin(phase_angle)

For a standard 12,000 BTU/h room air conditioner rated at CEER 12.0 on a 115V supply, real power draw is 12,000 / 12.0 = 1,000.0 W. At a default residential compressor power factor of PF = 0.92, apparent current is 1,000.0 / (115 * 0.92) = 9.45 A, giving 1,087 VA of apparent power and approximately 426 VAR of reactive power. By contrast, at the PF = 1.0 resistive lower bound, current drops to 8.70 A, apparent power equals 1,000 VA, and reactive power is 0 VAR.

How Do Inductive and Capacitive Loads Exchange Reactive Energy?

Inductive components absorb lagging reactive power to build and collapse magnetic fields, whereas capacitive components supply leading reactive power to store and release electric charge. In residential cooling equipment, compressor and blower motor windings act as inductive loads that cause current to lag behind voltage.

Manufacturers pair permanent-split-capacitor (PSC) motors with run capacitors so the leading capacitive current partially cancels the lagging inductive current inside the unit. That local energy exchange lowers the net phase angle seen at the wall receptacle, reducing reactive power draw (VAR) and bringing apparent current closer to the real-power minimum.

What Is the Difference Between Reactive Loading and Harmonic Distortion?

Pure reactive loading shifts a smooth sinusoidal current waveform out of phase with voltage, whereas harmonic distortion warps the current waveform itself through non-linear electronic switching. Both phenomena lower total power factor and increase supply current, but only the fundamental phase shift represents true sinusoidal VAR.

Fixed-speed induction compressors primarily create displacement power factor through inductive reactive loading. Variable-speed inverter mini-splits and modern ECM fan motors use rectifier and switching stages that draw non-sinusoidal current pulses; unless corrected by active power-factor correction (PFC), that distortion adds harmonic current that cannot be eliminated by simple capacitance alone.

How Does Reactive Power Affect US Branch-Circuit Sizing?

Circuit breakers and branch conductors heat up based on total apparent current (A) rather than real watts (W) alone, so reactive power consumes usable circuit headroom without delivering extra cooling. Never treat nominal VA ceilings as power-factor-free real-watt limits when checking whether a unit fits a residential branch circuit.

Circuit Rating Continuous Current (80% NEC) Apparent Power Limit (VA) Real-Watt Ceiling at PF = 0.92
15A @ 115V / 120V 12 A 1,380 VA / 1,440 VA ~1,270 W (at 115V)
20A @ 115V / 120V 16 A 1,840 VA / 1,920 VA ~1,693 W (at 115V)
15A @ 230V / 240V 12 A 2,760 VA / 2,880 VA ~2,540 W (at 230V)
20A @ 230V / 240V 16 A 3,680 VA / 3,840 VA ~3,386 W (at 230V)
30A @ 230V 24 A 5,520 VA ~5,078 W

On 208V multi-family electrical service, continuous VA headroom is 13.3% lower than on 240V service (for example, a 15A 208V circuit provides 2,496 VA continuous, or ~2,296 W real at PF = 0.92). Under NEC 440.62(C), any cord-and-plug room air conditioner sharing a branch circuit with lighting, other appliances, or general-use receptacles is capped at 50% of the branch rating (7.5A nameplate on a 15A branch, 10A on a 20A branch), and combined loads must remain within the 80% total ceiling. Always verify breaker ampacity from the exterior panel directory, the breaker handle, or a licensed electrician rather than inferring it from a wall receptacle shape, because NEMA 5-15R outlets are permitted on 20A branches under NEC 210.21(B)(3). Meeting an 80% loading threshold or using a dedicated circuit reduces nuisance tripping risk, though neither condition guarantees zero trips.

What Are Common Misreadings of Reactive Power (VAR)?

Most residential electrical miscalculations happen when reactive power is confused with billed energy consumption, resistive heater ratings, or thermal cooling capacity.

  • Treating VA limits as real watts: Dividing a 1,440 VA (120V, 15A continuous) ceiling by 1.0 ignores the inductive phase current carried by the wire; at PF = 0.92, real power headroom is closer to ~1,270 W at 115V.
  • Expecting VAR to appear on residential kWh bills: US residential utility meters bill real energy in kWh ((Watts / 1000) * hours_per_day * duty_factor * days), not VARh, although elevated current still increases minor resistive heating losses in branch wiring.
  • Confusing electrical VAR with cooling capacity or efficiency: Cooling output is measured in BTU/h or tons (1 ton = 12,000 BTU/h), while CEER, EER2, and SEER2 are efficiency ratios in BTU/Wh; none of these metrics measure reactive power.

Where Can You Calculate Apparent Current and Circuit Load?

To see how reactive power combines with real watts to set total circuit demand, compare apparent power (VA), model your unit's current draw in the AC Electricity and Amps Calculator, review branch limits in the Electrical and Energy Guide, or browse related terms in the CoolingSpecs Glossary.

More in this topic