Glossary / Technical reference

What Is Cooling Coil Bypass Factor?

Cooling coil bypass factor (BF) is the dimensionless fraction of supply air passing through a cooling coil that retains its entering-air temperature and humidity instead of reaching the coil's effective surface temperature, known as the apparatus dew point (ADP). It does not measure equipment energy efficiency (such as CEER, EER2, or SEER2), total cooling capacity in BTU/h or tons, or outdoor air leaking around a window frame. Higher indoor fan velocity, fewer tube rows, wider fin spacing, and uneven airflow across dirty fins all push the bypass factor upward, reducing moisture removal per pass.

How Is Coil Bypass Factor Calculated?

Coil bypass factor equals the temperature difference between the leaving air and the apparatus dew point divided by the temperature difference between the entering air and the apparatus dew point.

Bypass Factor (BF) = (T_leaving - T_ADP) / (T_entering - T_ADP)
Contact Factor (CF) = 1 - BF
  • Units: Dimensionless fraction from 0.00 to 1.00 when all temperatures are entered in consistent units (°F).
  • Apparatus dew point (T_ADP): The effective average surface temperature of the wetted evaporator coil fins.
  • Contact factor (CF): The complementary fraction of air that effectively reaches the coil's surface condition.

Worked residential example: Suppose indoor air enters a room air conditioner or mini-split evaporator at 80 °F dry-bulb and leaves at 58 °F dry-bulb while the coil operates at a 50 °F apparatus dew point.

BF = (58 - 50) / (80 - 50) = 8 / 30 = 0.27
CF = 1 - 0.27 = 0.73

In this condition, 27% of the airstream effectively bypasses the coil surface condition, while 73% achieves thermal and moisture contact.

How Do Coil Design and Airflow Shift Bypass Factor?

Increasing air velocity across the evaporator or reducing finned surface area raises the bypass factor, whereas slower face velocity and deeper multi-row coils lower it.

Physical Variable Shift in Bypass Factor Heat & Mass Transfer Mechanism
Higher fan speed (higher CFM) Increases BF Shorter air residence time over the fins reduces thermal contact per pass
Lower fan speed (lower CFM) Decreases BF Longer air residence time brings leaving air closer to the apparatus dew point
More coil tube rows / denser fins Decreases BF Greater total finned surface area increases contact probability and air-side pressure drop
Fewer tube rows / wider fin pitch Increases BF Less surface area per cubic foot of air leaves a larger core stream untouched
Clogged filter or matted coil Increases effective BF Uneven air distribution forces air at high local velocity through remaining open gaps

Changes in air density at higher elevations also alter mass flow rate for a given volumetric fan speed (CFM), slightly shifting sensible heat transfer across the fin surface.

How Does Bypass Factor Affect Sensible and Latent Cooling?

A lower bypass factor pulls leaving air closer to the apparatus dew point, increasing latent moisture removal relative to sensible temperature drop.

For dehumidification to occur, the coil's apparatus dew point must sit below the dew-point temperature of the entering room air. Typical residential room AC and ductless mini-split evaporators operate near a 0.15 to 0.30 bypass factor depending on coil depth and selected fan speed:

  • High fan speed: Raises BF, maximizes total CFM, and favors sensible cooling (lowering dry-bulb temperature) with less moisture condensed per pass.
  • Low fan speed: Lowers BF, increases contact time, and improves latent dehumidification per pass, provided airflow stays high enough to keep the coil above freezing.
  • Oversized capacity: Even with a low BF, a unit sized far above the room's cooling load satisfies the dry-bulb thermostat too quickly to sustain steady moisture removal. Match unit capacity to room load using the BTU calculator and room AC sizing guide.

What Are Common Misreadings of Coil Bypass Factor?

Coil bypass factor describes incomplete heat-and-mass transfer inside the evaporator fin pack, not physical air leakage around the cabinet or electrical efficiency.

  • Not window-frame or sleeve infiltration: Bypass factor measures air moving through the evaporator core without reaching ADP; unconditioned outdoor air entering around side curtains or wall sleeves is an enclosure sealing issue covered in windows and mounting.
  • Not an efficiency metric: CEER, EER, EER2, and SEER2 measure cooling output per watt-hour of electrical input (BTU/Wh), whereas BF is strictly an air-side psychrometric contact ratio.
  • Not a standalone capacity indicator: A very low bypass factor caused by severely choked airflow does not increase total BTU/h output; restricted airflow lowers total mass flow and risks evaporator icing.

More in this topic