What Is Wet-Bulb Temperature?
Wet-bulb temperature (°F, or °C) measures the lowest air temperature achievable through water evaporation alone at constant atmospheric pressure, reflecting both evaporative cooling potential and total air heat content (sensible heat plus moisture). It does not measure dry-air thermostat temperature (dry-bulb), cooling capacity (BTU/h), or equipment efficiency (CEER, EER2, or SEER2). Ambient dry-bulb temperature and relative humidity (RH) shift wet-bulb temperature directly: drier air produces a lower wet-bulb reading, while rising humidity pushes it closer to the dry-bulb temperature.
How Is Wet-Bulb Temperature Measured and Expressed?
Wet-bulb temperature is measured in °F (°C) by passing moving air over a wetted thermometer wick, where water evaporation absorbs latent heat from the surrounding air until saturation equilibrium is reached.
The gap between dry-air temperature and wet-bulb temperature defines the available evaporative cooling potential:
Wet-Bulb Depression (°F) = Dry-Bulb Temperature (°F) - Wet-Bulb Temperature (°F)- At 100% RH,
Wet-Bulb Temperature (°F) = Dry-Bulb Temperature (°F), leaving zero wet-bulb depression and zero evaporative cooling potential. - Lower ambient RH widens wet-bulb depression, allowing evaporative heat transfer to drop supply-air temperature farther below the outdoor dry-bulb reading.
How Does Outdoor Humidity Limit Evaporative Cooling?
Evaporative coolers stop cooling effectively above ~50% outdoor RH because elevated ambient moisture shrinks wet-bulb depression and prevents water from evaporating fast enough to lower indoor temperatures.
Because evaporative coolers rely on phase-change heat transfer rather than a vapor-compression refrigerant cycle, their maximum theoretical supply-air temperature is bounded by the outdoor wet-bulb temperature:
| Outdoor RH Condition | Wet-Bulb vs. Dry-Bulb Gap | Evaporative Cooling Performance |
|---|---|---|
| Low RH (below ~30%) | Wide wet-bulb depression | Strong temperature drop across the wetted media |
| Moderate RH (~30%–50%) | Narrowing wet-bulb depression | Reduced cooling output; noticeable indoor humidity rise |
| High RH (above ~50%) | Minimal wet-bulb depression | Ineffective cooling; adds moisture without meaningful temperature drop |
In humid conditions or enclosed rooms without continuous air exhaust, evaporative units raise indoor moisture levels without delivering the sensible temperature drop expected from refrigerated room air conditioner types.
Why Does Wet-Bulb Temperature Matter for Refrigerated Air Conditioners?
Higher indoor wet-bulb temperature increases the latent moisture burden on refrigerated window air conditioners, portable units, and mini-splits, forcing the evaporator coil to spend more of its capacity condensing water vapor rather than lowering the dry-bulb temperature.
When warm, humid air crosses a cold evaporator coil below its dew point, moisture condenses out of the airstream and releases latent heat into the coil. Under high wet-bulb conditions, a larger share of the unit's rated BTU/h goes toward latent dehumidification, leaving less sensible capacity to drop the thermostat reading. Standard room sizing still starts with floor area, ceiling height, sun exposure, insulation, and occupant heat-gain modifiers in the BTU Calculator and Sizing Guide, while wet-bulb conditions explain why humid spaces feel harder to cool at a given BTU/h rating.
What Are Common Misreadings of Wet-Bulb Temperature?
Treating wet-bulb temperature as interchangeable with dry-bulb temperature, dew point, or BTU/h cooling capacity leads to choosing ineffective evaporative coolers in humid climates or misjudging refrigerated AC performance.
| Metric | What It Measures | Key Difference from Wet-Bulb Temperature |
|---|---|---|
| Dry-bulb temperature (°F) | Sensible air temperature read on a standard thermometer | Ignores air moisture and evaporative cooling potential |
| Dew point temperature (°F) | Temperature at which air reaches 100% RH through cooling alone | Equal to or lower than wet-bulb temperature except at 100% RH, where all three match |
| Cooling capacity (BTU/h or DOE SACC) | Rate of heat removal from a space | Measures equipment heat-transfer rate, not the psychrometric state of the air |
| Efficiency rating (CEER, EER2, SEER2) | Ratio of cooling output to electrical input (BTU/Wh) | Measures electrical efficiency, never ambient air moisture or capacity |
Related Engineering Terms and Calculators
- Browse all thermodynamic and electrical definitions in the HVAC Glossary.
- Review related airflow properties, including Air Density, Air Changes per Hour, and Air-Side Pressure Drop.
- Size room equipment by floor area and heat-gain modifiers using the BTU Calculator.
- Compare evaporative limits against refrigerated window, portable, and mini-split systems in AC Types, System Comparisons, and Common Cooling Problems.