RLA vs. LRA: Reading Air Conditioner Running and Locked-Rotor Amps

Rated Load Amperes (RLA) represents continuous compressor current under normal operating load, whereas Locked Rotor Amperes (LRA) marks the peak transient draw when the motor starts from rest. Fixed-speed compressors draw a brief 3x to 6x LRA surge during startup before settling near RLA, while inverter-driven compressors ramp speed electronically and start near or below RLA; high outdoor temperatures, low supply voltage (such as 208V multi-family service), or restarting against unequalized refrigerant head pressure increase both actual running draw and startup surge duration.

Branch load versus current limitsBranch circuit load15 A breaker1 AOther load9.45 A ยท PF 0.92Combined current: 10.45 A50%80%100%Shared AC cap 7.5 A12 A continuous
Branch circuit reference

How do RLA, FLA, and LRA differ on an AC nameplate?

Each nameplate current rating describes a specific motor and operating state, so you must separate continuous running loads from instantaneous startup demand rather than treating any single number as total unit draw.

Nameplate Rating Full Name Component Covered Operating State Typical Magnitude Engineering Role
RLA Rated Load Amperes Compressor motor Continuous cooling or heating under rated conditions Baseline steady-state compressor draw Steady-state branch budgeting and thermal load estimation
FLA Full Load Amperes Condenser or evaporator fan motor(s) Continuous fan operation at rated speed Typically 0.3A to 2.5A on residential units Added to compressor RLA to determine total unit running amps
LRA Locked Rotor Amperes Compressor motor Instantaneous startup from rest (locked shaft) Typically 3x to 6x RLA on fixed-speed units Startup voltage-dip checks and generator/inverter surge sizing

Compressor RLA and fan-motor FLA run concurrently during normal cooling, so total steady-state unit current equals RLA + FLA rather than RLA alone. Because RLA is a maximum continuous rating under elevated load conditions rather than a fixed real-time measurement, actual steady-state current at mild outdoor temperatures often sits lower than nameplate RLA, which you can cross-check against efficiency-derived running power using the AC Electricity and Amps Calculator.

How do RLA and LRA translate into startup-transient inputs?

Translating nameplate amperage into electrical startup inputs depends on whether the compressor is fixed-speed or inverter-driven, because only fixed-speed motors experience a full-voltage locked-rotor inrush.

Compressor Architecture Startup Current Profile Transient Duration Steady-State Calculation Input Startup Surge Input
Fixed-speed (PSC / single-stage) Immediate spike up to full nameplate LRA 0.1 to 0.5 seconds (longer under low voltage) RLA + FLA (or Amps_apparent = Watts / (Voltage * PF)) Nameplate LRA + FLA (peak VA = Voltage * (LRA + FLA))
Inverter-driven (variable-speed mini-split / U-shaped) Soft electronic ramp from low frequency Gradual ramp over 5 to 30 seconds RLA + FLA ceiling Near RLA + FLA (no uncontrolled LRA spike)

When converting cooling capacity and efficiency into steady-state current for comparison against nameplate RLA + FLA, separate real power from apparent current using power factor (PF = 0.92 default for inductive motor loads, versus PF = 1.0 as a resistive lower bound):

  • Watts = BTU_h / EER_or_CEER
  • Amps_apparent = Watts / (Voltage * PF)

For example, a 12,000 BTU/h unit at CEER 12.0 on 115V draws 1,000.0 W real power, corresponding to 8.70 A at PF = 1.0 and 9.45 A at PF = 0.92, whereas its nameplate RLA + FLA covers worst-case high-ambient operation. For hardwired mini-splits and multi-zone condensers, nameplate Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) govern branch-circuit conductor and breaker selection for a licensed electrician; see the electrical and energy reference for those protection rules. Use nameplate LRA directly when evaluating fixed-speed compressor surge, estimating startup current limits, or entering backup power startup inputs for a portable generator or battery inverter.

How do you read nameplate amps and verify branch headroom?

Verify total running current against actual breaker ampacity from the electrical panel directory rather than guessing circuit capacity from the wall outlet shape.

  1. Record nameplate electrical values: Read the data plate on the unit chassis or condenser side panel and log rated voltage (115V, 208V, or 230V), compressor RLA, fan FLA, and compressor LRA.
  2. Calculate total steady-state unit amps: Add RLA + FLA for the unit's worst-case continuous draw, and convert wattage to apparent amps (Amps_apparent = Watts / (Voltage * PF) at PF = 0.92) if comparing normal-load draw across units.
  3. Verify breaker ampacity from the panel: Check the exterior panel directory, the breaker handle rating, or ask a licensed electrician. Never infer breaker rating from the wall receptacle shape, because NEMA 5-15R outlets are permitted on 20A branch circuits under NEC 210.21(B)(3); review plug and outlet pairings in the NEMA plug and receptacle matrix.
  4. Compare against NEC 80% continuous and 50% shared-branch limits: Check that continuous running load fits within 80% of the verified branch rating (or 50% under NEC 440.62(C) if any cord-and-plug room AC shares the circuit with lighting or general receptacles, while combined loads remain inside the 80% ceiling). On 208V multi-family service, continuous VA headroom is 13.3% lower than at 240V (for example, a 15A 208V circuit provides 2,496 VA / ~2,296 W real at PF = 0.92). Staying within 80% continuous loading or using a dedicated circuit satisfies the NEC sizing baseline, not a guarantee against breaker trips, because locked-rotor stalls, weak breakers, or voltage sags can still trip overcurrent protection.
  5. Check startup transient compatibility: Compare LRA + FLA against your circuit startup load limits and backup power surge rating to confirm whether a fixed-speed compressor's inrush will cause severe voltage dip or nuisance tripping.
Verified Branch Circuit 80% Continuous Current Limit Continuous Apparent VA Ceiling Real-Watt Ceiling (PF = 0.92) Shared-Branch Room AC Cap (NEC 440.62(C))
15A @ 115V / 120V 12.0 A 1,380 VA @ 115V / 1,440 VA @ 120V ~1,270 W @ 115V 7.5 A nameplate max
20A @ 115V / 120V 16.0 A 1,840 VA @ 115V / 1,920 VA @ 120V ~1,693 W @ 115V 10.0 A nameplate max
15A @ 230V / 240V 12.0 A 2,760 VA @ 230V / 2,880 VA @ 240V ~2,540 W @ 230V Dedicated or hardwired per unit listing
20A @ 230V / 240V 16.0 A 3,680 VA @ 230V / 3,840 VA @ 240V ~3,386 W @ 230V Dedicated or hardwired per unit listing
30A @ 230V 24.0 A 5,520 VA @ 230V ~5,078 W @ 230V Dedicated or hardwired per unit listing

What real-world failure modes push running or startup current above nameplate ratings?

Electrical and mechanical faults prevent a motor from clearing its startup phase quickly or force steady-state draw past RLA, causing thermal overload or breaker trips even on properly sized circuits.

  • Short-cycling against unequalized head pressure: Restarting a fixed-speed compressor within 3 to 5 minutes of shutdown forces the motor to push against high discharge pressure, stalling the rotor so LRA persists long enough to trip the internal thermal overload or branch breaker.
  • Low supply voltage (208V service or line sag): Under-voltage during startup reduces motor torque while increasing current draw, stretching the LRA window and driving steady-state running amps above nominal 230V RLA values.
  • Degraded run or start capacitor: A weak capacitor reduces phase-shift starting torque on single-phase compressors, extending LRA duration and elevating running current above RLA until the compressor overheats.
  • Coincident loads on shared branches: Even when a room AC sits under the 7.5A (15A branch) or 10.0A (20A branch) NEC 440.62(C) shared-circuit cap, an LRA startup spike coinciding with a vacuum, space heater, or microwave cycle can exceed the breaker's magnetic or thermal trip curve.
  • Restricted airflow or fouled condenser coil: High condensing temperatures raise compressor head pressure, pushing continuous operating current toward or beyond nameplate RLA.

DIY Scope vs. Licensed Pro Thresholds

Homeowners can safely inspect exterior data plates, calculate apparent current, and size backup generators, whereas any work inside electrical panels, hardwired circuits, or pressurized refrigerant lines requires licensed specialists.

Task Category Homeowner / Non-Licensed Scope Licensed Electrician Scope EPA Section 608 Certified HVAC Technician Scope
Nameplate & Load Math Reading RLA, FLA, LRA, and V; computing RLA + FLA and Amps_apparent Interpreting MCA and MOP for branch-circuit and disconnect installation Evaluating compressor amp draw against refrigerant operating pressures
Circuit & Panel Work Reading exterior panel directory labels; plugging UL-listed LCDI cords into verified outlets (never use ordinary extension cords or bypass LCDI plugs) Opening electrical panels, verifying unlabeled breakers, pulling new 120V/240V circuits, replacing receptacles, wiring hardwired disconnects None (electrical distribution work remains with a licensed electrician)
Refrigerant & Mechanical Cleaning washable air filters and exterior cabinet grilles None Connecting, opening, or disconnecting pressurized or pre-charged refrigerant lines or service valves; flaring, leak-testing, evacuating, or charging refrigerant