Compare / Technical reference

EER vs. EER2 Mini-Split Peak Cooling Efficiency Ratings

Use EER2 when evaluating 95°F full-load peak cooling efficiency on current mini-split specifications, because non-ducted wall, cassette, and floor heads align closely with legacy EER while concealed short-duct terminals test lower under DOE Appendix M1 static pressure rules. Both EER and EER2 express cooling efficiency in BTU/Wh at 95°F outdoor conditions and never represent cooling capacity in BTU/h or tons.

EerEer rating basisStandardized test ratingCapacity / electrical energy
Eer
Eer2Eer2 rating basisStandardized test ratingCapacity / electrical energy
Eer2

When Does EER2 Win vs. Legacy EER?

EER2 is the standard choice for any current equipment selection or rebate check, whereas legacy EER only applies when reading pre-2023 specifications or legacy documentation.

Decision Criterion Choose EER2 (Appendix M1) Choose Legacy EER (Appendix M)
Current Equipment & Rebates Wins for all 2023-and-newer mini-split spec sheets, ENERGY STAR thresholds, and utility peak-efficiency rebates. Outdated for current incentive compliance; utilities and federal programs reference EER2.
Concealed Short-Duct Heads Wins by capturing realistic blower watt draw against higher external static pressure (ESP). Overstates peak efficiency on short-ducted indoor units tested at lower static pressure.
Non-Ducted Heads (Wall, Cassette, Floor) Wins for current spec alignment; numerical values match legacy EER closely. Equivalent only when comparing older pre-2023 non-ducted models to each other.
Historical Spec Matching Requires conversion or updated submittals when matching older engineering schedules. Wins only when auditing or matching legacy pre-2023 equipment documentation.

How Do EER and EER2 Compare Across Testing and Specs?

Both metrics measure steady-state, full-load cooling efficiency at 95°F outdoor dry-bulb and 80°F indoor dry-bulb (67°F wet-bulb), diverging primarily in how Appendix M1 handles external static pressure on ducted indoor units.

Dimension EER (Legacy Appendix M) EER2 (Current Appendix M1)
Governing Test Procedure 10 CFR Part 430, Subpart B, Appendix M 10 CFR Part 430, Subpart B, Appendix M1
Peak Test Conditions 95°F (35.0°C) outdoor dry-bulb; 80°F dry-bulb / 67°F wet-bulb indoor 95°F (35.0°C) outdoor dry-bulb; 80°F dry-bulb / 67°F wet-bulb indoor
External Static Pressure (ESP) Lower static pressure baseline for ducted/short-ducted terminals Higher, more representative ESP requirements for ducted and concealed short-ducted terminals
Non-Ducted Mini-Split Impact Free-blow operation (0.00 in. w.c. ESP) Free-blow operation (0.00 in. w.c. ESP); numbers remain nearly identical to EER
Short-Ducted Mini-Split Impact Higher rated efficiency due to lower blower power penalty Lower rated efficiency because blower watts increase to overcome higher ESP
Measurement Units BTU/Wh (Cooling BTU/h divided by Total Input Watts) BTU/Wh (Cooling BTU/h divided by Total Input Watts)
Capacity vs. Efficiency Role Efficiency ratio only; never indicates cooling capacity Efficiency ratio only; never indicates cooling capacity

Why Do Non-Ducted and Concealed Mini-Splits Diverge Under EER2?

Non-ducted mini-split heads discharge air directly into the room with zero external ductwork, so their EER2 rating tracks legacy EER closely, whereas concealed short-duct terminals incur a blower-power penalty under Appendix M1.

Under Appendix M1, ducted and concealed short-duct indoor units must maintain rated airflow against higher external static pressure to reflect real-world supply plenums, short runs, and return grilles. Because fan power scales upward with static pressure, total input watts (W) rise for the same BTU/h cooling output, pulling the EER2 ratio down compared to the older EER test. Free-blow wall-mounted, floor-console, and ceiling-cassette heads have no external duct resistance, so their fan watt draw and resulting EER2 values remain closely aligned with legacy EER.

How Do EER and EER2 Translate Into Peak Running Watts and Amps?

Dividing rated cooling output by EER or EER2 gives the 95°F full-load input power in watts, which converts directly to estimated running current for electrical planning.

Use the following plain-text equations to estimate full-load peak demand at 95°F:

  • Watts = BTU_h / EER_or_EER2
  • Amps_apparent = Watts / (Voltage * PF)

Keep the power factor (PF = 0.92 default for compressor/inverter loads and PF = 1.0 resistive lower bound) separate from nameplate Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP), which a licensed electrician uses for branch-circuit sizing.

For example, an 18,000 BTU/h (1.5-ton) non-ducted mini-split rated at EER2 12.5 on a 230V circuit draws:

  • Watts = 18,000 / 12.5 = 1,440.0 W
  • At PF = 1.0 (resistive lower bound): Amps_apparent = 1,440.0 / (230 * 1.0) = 6.26 A
  • At PF = 0.92 (default): Amps_apparent = 1,440.0 / (230 * 0.92) = 6.81 A

If a concealed short-duct version of the same 18,000 BTU/h system drops from EER 12.5 to EER2 11.7 under Appendix M1 static pressure rules, full-load peak power rises to 1,538.5 W (6.69 A at PF = 1.0, or 7.27 A at PF = 0.92 on 230V).

When Does Relying on EER or EER2 Cause a Misfit?

Each rating fails when applied outside its intended test scope, equipment vintage, or operating profile.

Legacy EER misfit cases:

  • Rebate and code verification: Submitting a legacy EER figure for a utility rebate or incentive that requires an Appendix M1 EER2 threshold causes disqualification.
  • Cross-generation short-duct comparisons: Comparing a pre-2023 concealed short-duct model's EER directly against a current model's EER2 penalizes the newer unit unfairly on paper.

EER2 misfit cases:

  • Whole-season energy cost estimates: Relying on 95°F full-load EER2 to project annual kWh in mild or moderate climates ignores part-load inverter efficiency; use SEER vs. SEER2 for seasonal cooling energy.
  • Window AC cross-shopping: Comparing a mini-split's EER2 directly to a window AC's CEER mixes two different test procedures, because CEER includes standby and off-mode power while EER2 measures active 95°F full-load cooling.
  • Room sizing decisions: Treating a high EER2 number as extra cooling power is a category error—room coverage still depends on BTU/h load, ceiling height, sun exposure, and insulation.

What Should You Check Next?

Use these related standards and sizing tools to complete your mini-split evaluation:

More in this topic